-/60/30 Sliding Fire Door

Rating: -/60/30

System: Forster Fuego Light Insulated Steel Framing

Incorporating Forster fuego light steel framing system with Pilkington Pyrostop® fire rated glass, these sliding fire doors have been tested and approved to AS1530.4 for fire resistance up to -/60/30 FRL.

Suited for applications that require certified resistance against the spread of fire, whilst retaining the safety and aesthetics of a fully transparent single or double automatic fire rated sliding door. Approved for inclusion within both solid and glazed fire rated walls, with large side and top lites available in a range of FRLs.

Features

  • Fire resistance to -/60/30 certified to AS1530.4
  • Single and pair configurations
  • Assa Abloy SL500 motorised mechanism
  • Single leaves to 2760 high x 1150 wide, or 2500 high x 1240 wide
  • Overall opening for pairs up to 2760 high x 2312 wide or 2500 high x 2492 wide
  • Approved for installation in a variety of wall types, including masonry walls, lightweight plaster walls, and full integration with glazed top and side lites with FRLs of -/60/30, -/60/60, -/90/90, -/120/120 using forster fuego light or forster thermfix vario curtain wall profile systems
  • Class A impact rated 18mm Pilkington Pyrostop® glass
  • Suitable for internal or external applications (provided mechanism is protected from weather)
  • Powder coated or paint finish to mild steel frame
  • System must be activated by FIP or certifier approved system
  • Optional vertical and horizontal internal rails
  • Upgrade to low iron 23mm (internal) or 27mm Pilkington Pyrostop® Optiwhite
  • DWG and DXF drawings, and full architectural support available from TPS

Dimensions Graph

Technical Specifications

Max leaf height (H)Max leaf width (W)Pair configuration max width (PDW)Max door leaf area (H x W)Max glass pane heightMax glass pane widthMax glass pane area
Option 1 H1/W12760mm1150mm2312mm3.17m22604mm1014mm2.64m2
Option 2 H2/W22500mm1240mm2492mm3.10m22344mm1104mm2.58m2

How To Specify

Fire rated sliding door assembly to be tested and certified TPS -/60/30 sliding glazed fire door incorporating insulated forster fuego light steel frame with 18mm Pilkington Pyrostop® fire rated glazing, Assa Abloy SL500 motorised mechanism, fully insulated and controlled by the FIP or alternative to meet the requirements of the relevant certifying authority.
Contact Technical Protection Systems Pty Ltd for further information.

CONTACT US

Phone: (03) 9720 1930
Fax: (03) 9720 1929
web@technicalprotection.com.au
2/21 Malvern St, Bayswater Victoria 3153

Send us your enquiry / Trade enquiries welcome

Send us your query today and a member of our team will get in touch. 

    Specifier (e.g., architect, draftsperson, etc.)*BuilderFabricatorOwner BuilderOther

    Follow us on Instagram